Received date: 2003-02-21
Online published: 2010-10-01
By investigation and research on the new type sewage purifier, it is confirmed that the main factors that make treatment capacity less than design capacity are resulted from many internal defects. After modifying the washer, drainage washing pump, filter frame, pyramidal reactor and filter cap, the turbidity of the purified water can be descended to 12 ~ 19 mg/L. Its capacity can reach the design capacity.
Key words: sewage; purifier; coagulating reaction; washer; drainer
Liu Yachong, Wang Kai . Improvement of new type sewage purifier[J]. Industrial Water Treatment, 2004 , 24(2) : 70 -71 . DOI: 10.11894/1005-829x.2004.24(2).70
[1]严煦世.给水排水工程快速设计手册:给水工程[M].北京:中国建筑工业出版社,1995.205-304
[2]于尔捷,张杰.给水排水工程快速设计手册:排水工程[M].北京:中国建筑工业出版社,1996.227-232
[3]高湘.给水工程技术及工程实例[M].北京:化学工业出版社,2002.122-172
/
〈 |
|
〉 |