Ti/RuO2-IrO2电极电催化氧化处理钴湿法冶金废水研究
Research on the treatment of cobalt hydrometallurgical wastewater by Ti/RuO2-IrO2 electrode electrocatalytic oxidation
收稿日期: 2019-03-4
Received: 2019-03-4
作者简介 About authors
廖力锐(1994-),硕士电话:18222332096,E-mail:
为解决钴湿法冶金废水中较高的有机物影响Na2SO4回收质量问题,开展了电催化氧化处理钴湿法冶金废水研究。以COD去除率为考核指标,通过单因素实验,探讨了COD去除率与反应时间、电流密度、反应初始pH和极板间距的关系;通过响应面优化实验,得到目标范围内的最佳处理条件,在此条件下,COD去除率可达71.72%。结合反应能耗再次进行优化实验,优化条件下,COD去除率为69.75%,反应平均能耗为0.173 5 kW·h/g。
关键词:
In order to solve the problem that the comparatively high organic matter content in cobalt hydrometallurgical wastewater affects the recovery quality of Na2SO4, the research on electrocatalytic oxidation treatment of this kind of wastewater has been implemented. Using the removing rate of COD as an assessment index, the relationship between COD removing rate and reaction time, current density, initial pH, plate spacing are discussed, based on a series of single-factor experiments. Through response surface optimization experiments, the optimal conditions within the target range have been obtained. Under these conditions, the COD removing rate can reach 71.72%. Combined with reaction energy consumption, the optimization experiments have been implemented again. Under the optimized conditions, the COD removing rate is 69.75%, and the average reaction energy consumption 0.173 5 kW·h/g.
Keywords:
本文引用格式
廖力锐, 刘东方, 黄文力, 王振东, 李文姣.
Liao Lirui.
1 实验部分
1.1 实验水质
实验用水取自天津市滨海新区某钴湿法冶金厂生产废水。主要水质指标:COD 1 400~1 500 mg/L,pH 12±0.1,色度128倍,Cl-(2.3±0.1)g/L,SO42- 80~90 g/L,外观呈可透过性淡黄色。废水中含有大量Na2SO4、NaCl等盐类,盐度极高;此外废水中还含有大量的表面活性剂、烷烃、芳香烃等,使废水呈极其稳定的乳化状态,处理难度很大。
1.2 实验装置
实验反应器由有机玻璃制成,容积0.45 L。反应器底部有固定极板的凹槽数条,盖子上有插孔,与底部凹槽一一对应。阴极为不锈钢电极,阳极为Ti/RuO2-IrO2电极,垂直插入溶液中。通过插孔和凹槽调整电极板间距。浸没在溶液中的单个电极表面积为60 cm2,两电极与直流电源相连。反应开始前,将反应器放置在磁力搅拌器上。
1.3 实验方法及分析
1.3.1 实验方法
1.3.2 分析测定方法
pH采用pH酸度计测定;COD采用快速消解分光光度法(HJ/T 399—2007)测定;色度采用稀释倍数法(GB 11903—1989)测定;Cl-采用硝酸银滴定法(GB 11896—1989)测定;SO42-采用铬酸钡分光光度法(HJ/T 342—2007)测定。
1.3.3 能耗计算
能耗计算公式:
式中:I——电流,A;
U——电压,V;
t——电解时间,h;
COD0——原水初始COD,mg/L;
CODt——反应t时刻的COD,mg/L;
V——废水体积,L。
2 结果与讨论
2.1 反应时间的确定
在电流密度为40 mA/cm2,pH为12,极板间距为20 mm的条件下,考察反应时间对COD去除率的影响,结果如图1所示。
图1
2.2 单因素实验结果分析
2.2.1 电流密度
在pH为12,极板间距为20 mm的条件下,考察电流密度对COD去除率的影响,结果如图2所示。
图2
图2表明,COD去除率随着电流密度的增大而增大;但当电流密度达到40 mA/cm2后,继续增大电流密度并不能显著提高COD去除率。这是因为电流密度较低时,电流密度越高,电解液中活性基团浓度越高,对有机物的氧化分解作用越强;同时,在电催化氧化体系中,有机物被·OH攻击容易生成聚合物附着于电极表面,进而阻碍自由基与分子接触氧化,而提高电流密度能减少聚合物的量〔9〕。但电流密度增加至一定程度后,即使在极板表面产生大量氧化基团,但受污染物扩散速率的限制,降解效果并不能明显提高,整体电流利用效率会有所下降〔10〕;同时电流密度过大会产生副反应,实验过程中可以明显看到极板周围聚集较多气泡,废水析氧、析氢现象严重,使得电解能耗增加。
2.2.2 反应初始pH
溶液pH可以直接改变溶液与电极界面的双电层结构、活性物质的种类以及活性物质与有机物的相互作用,进而影响电催化氧化效果〔9〕。考虑到实际生产中该废水呈碱性,故在电流密度为40 mA/cm2,极板间距为20 mm,初始pH为7、9、11、13的条件下进行电催化氧化实验,考察初始pH对COD去除率的影响。结果表明,pH从7升到13,COD去除率仅下降了2.54%,从中性到碱性,COD去除率的变化并不大。有文献〔8〕表明,随着pH的升高,析氧副反应加剧,·OH的生成量减少,其氧化作用减弱。但与此同时pH升高,可使阳极产生的Cl2在溶液中的溶解度增加,产生游离氯的量也随之增加〔11〕,ClO-的氧化作用增强,从一定程度上弥补了因为·OH的氧化作用减弱导致的COD去除率下降,从而使COD去除率的变化不大。
2.2.3 极板间距
在电流密度为40 mA/cm2,pH为12的条件下,考察极板间距对COD去除率的影响,结果如图3所示。
图3
2.3 响应面实验设计与结果分析
2.3.1 优化实验设计及结果
采用Box-Behnken设计实验,并借助Design-Expert 8.0进行响应面分析,对实验结果进行优化。以COD去除率(Y)为因变量,以电流密度(A)、反应初始pH(B)、极板间距(C)为自变量(A、B和C均为实验水平实际值)的响应面实验结果见表2。
表2 Box-Behnken实验设计与结果
序号 | A | B | C | Y/% | |
真实值 | 预测值 | ||||
1 | 50 | 10 | 10 | 69.87 | 70.18 |
2 | 40 | 10 | 20 | 66.11 | 66.51 |
1 | 10 | 10 | 10 | 66.19 | 65.88 |
4 | 10 | 8 | 20 | 60.70 | 60.60 |
5 | 40 | 8 | 10 | 61.01 | 60.90 |
6 | 50 | 12 | 20 | 70.08 | 70.18 |
7 | 40 | 10 | 20 | 66.20 | 66.51 |
8 | 40 | 10 | 20 | 67.27 | 66.51 |
9 | 10 | 12 | 20 | 58.51 | 58.89 |
10 | 10 | 10 | 10 | 55.41 | 55.67 |
11 | 40 | 12 | 10 | 65.84 | 65.97 |
12 | 40 | 12 | 10 | 65.47 | 64.86 |
11 | 50 | 8 | 20 | 67.92 | 67.54 |
14 | 40 | 10 | 20 | 66.11 | 66.51 |
15 | 40 | 8 | 10 | 68.19 | 69.00 |
16 | 40 | 10 | 20 | 66.50 | 66.51 |
17 | 50 | 10 | 10 | 69.61 | 69.40 |
根据多项式回归分析对实验数据进行拟合,得到二次响应曲面方程:
二次响应面模型拟合的最佳反应条件:电流密度50 mA/cm2,极板间距10 mm,pH为12。
2.3.2 方差分析
使用数据处理软件Design-Expert 8.0对实验数据进行方差分析,结果见表3。
表3 回归方程的方差分析
变量 | 平方和 | 自由度 | 均方 | F值 | P值(Prob > F) |
模型 | 268.91 | 9 | 29.88 | 84.69 | < 0.000 1 |
A | 166.26 | 1 | 166.26 | 471.24 | < 0.000 1 |
B | 0.43 | 1 | 0.43 | 1.23 | 0.304 8 |
C | 42.55 | 1 | 42.55 | 120.61 | < 0.000 1 |
AB | 4.73 | 1 | 4.73 | 13.41 | 0.008 1 |
AC | 31.36 | 1 | 31.36 | 88.89 | < 0.000 1 |
BC | 12.22 | 1 | 12.22 | 34.62 | 0.000 6 |
A2 | 4.54 | 1 | 4.54 | 12.86 | 0.008 9 |
B2 | 5.92 | 1 | 5.92 | 16.77 | 0.004 6 |
C2 | 0.11 | 1 | 0.11 | 0.30 | 0.602 1 |
残差 | 2.47 | 7 | 0.35 | ||
失拟值 | 1.73 | 3 | 0.58 | 3.13 | 0.149 4 |
误差值 | 0.74 | 4 | 0.18 | ||
总和 | 282.30 | 16 |
注:R2=0.990 9,RAdj2=0.979 2,RPred2=0.893 6,信噪比=32.307。
由表3可知,模型的“Prob>F”值<0.000 1,模型极其显著;失拟项的“Prob>F”值>0.05,失拟项不显著,该模型可靠。R2=0.990 9,说明相关性好;RAdj2-RPred2=0.085 6<0.2,变异系数为0.91%<10%,模型的可信度和精密度高;信噪比为32.307,在合理范围内。由模型的方差分析结果可知,回归模型达到显著性水平。
另外,由表3可知,电流密度、极板间距对电催化氧化降解COD的线性效应显著,3个因素对COD去除率影响显著性为电流密度>极板间距> pH。
2.3.3 双因子交互效应分析
图4
图5
图6
由图4可以看出,电流密度与pH的交互作用不明显。与pH相比,电流密度对COD去除率的影响更为显著。同时,在实验范围内,pH越高,电流密度的大小对COD去除率的影响越为明显,这可能是pH越高,ClO-的氧化作用越明显,而ClO-受电流密度的影响大的缘故。
由图5可以看出,电流密度与极板间距的交互作用明显。在极板间距一定的条件下,COD去除率随电流密度的增大而增大。在电流密度一定时,低电流密度下,COD去除率随极板间距的增大而增大;高电流密度下,COD去除率随极板间距的增大而减小。在极板间距为10 mm,电流密度为50 mA/cm2时,COD去除率最大。这是因为低电流密度下,COD去除率受平行极板对液体的黏滞作用的影响明显;高电流密度下,COD去除率受黏滞作用的影响减弱,受传质距离带来的传质阻力的影响较大。
由图6可以看出,pH与极板间距的交互作用较为明显。与pH相比,极板间距对COD去除率的影响稍大。
2.3.4 验证实验
根据软件优化得最佳工艺条件:电流密度50 mA/cm2,极板间距10 mm,pH为12。在此条件下,模型预测的COD去除率为72.26%。为对预测结果进行验证,采用上述条件进行3组重复实验,得到COD去除率分别为71.69%、72.08%和71.40%,平均值为71.72%,与预测值接近,相对误差为0.74%(<2%),拟合度较好,说明该模型具有指导意义。
2.4 能耗分析
表4 电流密度调整方案及结果比较
方案 | 电流密度/(mA·cm-2) | COD去除率/% | 平均能耗/ (kW·h·g-1) |
优化方案一 | 50(120 min)+40(60 min) + 30(60 min) | 69.75 | 0.173 5 |
优化方案二 | 50(120 min)+40(120 min) | 70.44 | 0.193 4 |
原方案 | 50(240 min) | 71.69 | 0.218 5 |
图7
实验结果表明,虽然优化方案一和优化方案二随着时间的延长,单位时间内的平均能耗也在不断增大,但方案一在180~240 min内的能耗远远低于原方案,方案一和方案二在120~180 min内的能耗也低于原方案。优化方案一与原方案相比,COD去除率降低不到2%,两者出水COD差值小于30 mg/L,但方案一的能耗不到原方案的80%。综合考虑能耗和COD去除效果,可选择优化方案一。以此条件对钴湿法冶金废水进行批量预处理,出水COD为400~450 mg/L,色度为16倍,Cl-为(0.4±0.1)g/L,COD去除率均高于68.7%,反应平均能耗约为0.174 kW·h/g。
3 结论
(1)单因素和响应面优化实验结果表明,在实验范围内,各因素对COD去除率影响的显著性顺序依次为电流密度>极板间距>反应pH;最佳工艺条件:电流密度50 mA/cm2,极板间距10 mm,pH为12。
(2)所建立的二次模型在研究区域内拟合效果好,显著性水平高,可信度和精密度高。在最佳条件下,COD去除率预测值为72.26%,实验值为71.72%,实验值与预测值的相对误差仅有0.74%。
(3)综合考虑能耗和COD去除效果,可选择如下优化方案:极板间距为10 mm,pH为12,电流密度为50 mA/cm2(120 min)+40 mA/cm2(60 min)+30 mA/cm2(60 min)。以此条件对钴湿法冶金废水进行批量预处理,出水COD为400~450 mg/L,色度为16倍,Cl-为(0.4±0.1)g/L,COD去除率均高于68.7%,反应平均能耗约为0.174 kW·h/g。
(4)该预处理工艺能大幅度降低钴湿法冶金废水中的COD和色度,能极大提高MVR回收Na2SO4的质量,同时Cl-含量明显降低,能缓解对后续设备的腐蚀。
参考文献
钴湿法冶炼废水水量水质估算方法探讨
[J].DOI:10.3969/j.issn.1004-4345.2017.01.013 [本文引用: 1]
MVR技术在湿法冶金废水处理中的应用
[J].DOI:10.3969/j.issn.1671-9654.2016.01.013 [本文引用: 1]
MVR技术在钴镍湿法冶炼废水处理中的应用
[J].DOI:10.3969/j.issn.1007-1865.2017.23.043 [本文引用: 1]
Electrocatalysis and electroanalysis of nickel, its oxides, hydroxides and oxyhydroxides toward small molecules
[J].
Ti/RuO2-SnO2-TiO2涂层电极电催化氧化苯酚废水研究
[J].
/
〈 |
|
〉 |
