火电厂湿式通风冷却塔向大气排放氯离子问题研究
|
苏跃进,董宝林
|
Study on chloride ion emission to the atmosphere from wet ventilation cooling tower of thermal power plants
|
Yuejin Su,Baolin Dong
|
|
表2 采用城市中水做补充水期间的水质检测结果 mg/L
|
|
|
检测项目 | t11 | t12 | t13 | t14 | t15 | t16 | t17 | t18 | t19 | 算术平均值 | 城市中水 | TDS | 660 | 862 | 569 | 973 | 1 047 | 890 | 780 | 961 | 1 160 | 878 | Cl- | 117 | 216 | 50 | 201 | 227 | 175 | 95 | 150 | 190 | 158 | SO42- | 128 | 239 | 240 | 240 | 320 | 158 | 133 | 350 | 368 | 242 | K+ | 28 | 46 | 10 | 53 | 56 | 39 | 31 | 40 | 58 | 40 | #1机组循环水 | TDS | 2 918 | 2 675 | 1 503 | 1 388 | 2 632 | — | 2 206 | — | 3 546 | 2 410 | Cl- | 704 | 636 | 289 | 184 | 550 | — | 410 | — | 800 | 510 | SO42- | 855 | 796 | 445 | 483 | 882 | — | 816 | — | 1 256 | 790 | K+ | 124 | 140 | 65 | 60 | 133 | — | 103 | — | 152 | 111 | #2机组循环水 | TDS | — | — | 1 314 | 2 302 | 2 708 | 1 864 | 2 500 | 4 238 | 2 695 | 2 517 | Cl- | — | — | 195 | 422 | 618 | 351 | 406 | 784 | 590 | 481 | SO42- | — | — | 486 | 701 | 828 | 575 | 944 | 1 792 | 952 | 897 | K+ | — | — | 36 | 105 | 137 | 87 | 116 | 168 | 120 | 110 |
|
|
|