基于感知-决策-评估的污水处理智能曝气方法
袁沐坤,于广平,刘坚,李健

Intelligent aeration method for wastewater treatment based on perception-decision-evaluation
Mukun YUAN,Guangping YU,Jian LIU,Jian LI
表2 优化系统和原始系统的出水情况及处理性能对比
Table 2 Comparison of effluent quality and treatment performance between optimized system and original system
项目COD/(g·m-3TSS/(g·m-3BOD5/(g·m-3TN/(g·m-3SNH/(g·m-3EQ/(kg·d-1EC/(kW·h·d-1
原始系统(晴)45.3412.412.6015.24.406 9429 443
原始系统(雨)45.1612.282.6115.884.9710 2009 443
原始系统(暴雨)45.4812.562.6115.594.928 4719 443
优化系统(晴)45.3612.422.6115.073.496 869(↓1.05%)8 377(↓12.73%)
优化系统(雨)45.1712.282.6115.744.0510 090(↓1.07%)8 103(↓14.1%)
优化系统(暴雨)45.4912.572.6115.43.998 325(↓1.72%)8 416(↓10.88%)