摘要:
以钛片为基底,SnO2+Sb2O5为中间层,自制氧化铅电极用于苯酚的电化学降解。试验结果表明,自制电极具有良好的苯酚去除效果:在室温为15℃,电极间距为15 mm,电流密度为16 mA/cm2,苯酚溶液pH为6.3,导电介质Na2SO4浓度为0.25 mol/L时,电解300 mL初始质量浓度为100 mg/L的苯酚,4 h后去除率可达91.89%。研究降解过程中苯酚初始浓度、pH、导电介质、电流密度、电极间距等因素对苯酚降解过程的影响。在此基础上对苯酚降解影响较大的初始浓度、pH、电流密度3个因素优化,通过响应曲面分析交互影响和单因素影响,结果表明,三者交互影响不大,苯酚初始浓度影响最大,pH影响最小,与单因素影响分析结果吻合。
关键词:
自制氧化铅电极,
苯酚,
电化学降解,
响应曲面法
Abstract:
Using titanium plate as substrate,and SnO2+Sb2O5 as an intermediary,the lead oxide electrode for electro-chemical degradation of phenol is made.The experimental results show that the homemade electrode has very good phenol removing effect.When the room temperature is 15℃,electrode spacing 15 mm,current density 16 mA/cm2,pH 6.3,and conductive medium Na2SO4 concentration 0.25 mol/L,300 mL of phenol,whose initial mass concentra-tion is 100 mg/L,is electrolyzed for 4 h,the removing rate can reach 91.89%.The influences of the factors,such as initial concentration of phenol,pH,conductive medium,current density,electrode spacing,etc.on the phenol degra-dation process are studied.On the basis of these results,the three factors that have more influences on phenol degra-dation,including initial concentration,pH and current density,are optimized,by response surface method,interac-tive influence and single-factor influence.The results show that the interactive influences of the three are not obvi-ous.The initial concentration of phenol has the largest influence,and pH has the least influence.It is in line with the analytical result of single factor influence.
Key words:
homemade lead oxide electrode,
phenol,
electrochemical degradation,
response surface method
中图分类号:
金贻芳, 于萍, 罗运柏. 自制氧化铅电极降解苯酚的试验研究[J]. 工业水处理, 2016, 36(5): 55-59.
Jin Yifang, Yu Ping, Luo Yunbai. Experimental study on the home-made lead oxide electrode for the degradation of phenol[J]. INDUSTRIAL WATER TREATMENT, 2016, 36(5): 55-59.