Abstract:
Compared with the current process of treating discharged circulating cooling water for reuse in heat power plants, a study on the processes, such as coagulation - ultrafiltration(UF) - reverse osmosis(RO) and clarification - filtration - UF - RO is carried out. The results show that, UF as the pretreatment of RO, has greater superoity. Although the treatment process can be simplified by using coagulation - UF - RO, the membrane flux is lower, and the general investment has not been lessened, but the operational reliability is low. The process of clarification - filtration - UF- RO has perfect effluent water quality ( the effluent SDI value of UF is less than 2, the desalination rate of RO is up to 99%) . UF membrane flux is up to 3 m3 /(m2·d) . The system runs reliably, and the maintenance cost is low. Therefore, it is a reasonable process.
Key words:
heat power plant,
circulating cooling water,
ultrafiltration,
reverse osmosis
摘要:
结合火力电厂循环冷却排水回用处理现有工艺,对混凝—超滤(UF)—反渗透(RO)工艺和澄清—过滤—UF—RO工艺进行了试验研究。结果表明,超滤作为RO的预处理具有较大的优越性,混凝—UF—RO工艺虽然可简化处理流程,但膜通量较小,总体投资并未减少,且运行可靠性较差;澄清—过滤—UF—RO工艺出水水质优良(UF出水SDI值小于2,RO除盐率达到99%),UF膜通量可达到3m3/(m2.d),系统运行可靠,运行维护费用低,是较合理的工艺。
关键词:
火力电厂,
循环冷却水,
超滤,
反渗透
CLC Number:
Li Fuqin, Tang Yuegang, He Xuwen, Wang Zhiqiang, Wang Jian. Study on the treatment of discharged circulating cooling water for reuse in heat power plants[J]. INDUSTRIAL WATER TREATMENT, 2005, 25(11): 37-39.
李福勤, 唐跃刚, 何绪文, 王志强, 王建. 火力电厂循环冷却排水回用处理工艺研究[J]. 工业水处理, 2005, 25(11): 37-39.