Abstract:
In power plants,the conductivity increase of effluent in demineralized water tanks occurs frequently. By means of theoretical calculation and case introduction,the causes have been analyzed in three aspects,including:the top sealing of demineralized water tank is not tight enough,the anticorrosion coating on the tank inner walls has many defects,and the equipment of boiler make-up water system may be abnormal. Based on these analyses,the co-rresponding solutions are brought forward.
Key words:
demineralized water,
conductivity,
polyurea elastomer
摘要:
除盐水箱出水电导率升高在电厂时有发生,针对除盐水箱出水电导率升高现象,通过理论计算和案例介绍,从3个方面进行了原因分析。分析原因包括:除盐水箱顶部密封不严,水箱内壁防腐层缺陷,以及锅炉补给水系统出现设备异常。在对各项原因进行分析的基础上,指出了相应的解决方法。
关键词:
除盐水,
电导率,
聚脲弹性体
CLC Number:
Li Hairong. Cause analysis and treatment of the conductivity increase of effluent in demineralized water tank[J]. INDUSTRIAL WATER TREATMENT, 2016, 36(2): 106-108.
李海荣. 除盐水箱出水电导率升高原因分析及处理[J]. 工业水处理, 2016, 36(2): 106-108.