Study on membrane technology used for the treatment of circulating cooling system discharge water of power plants
Received date: 2005-04-17
Online published: 2010-10-01
The ultra-filtration and reverse osmosis are used for the reuse of the circulating cooling system discharge water from power plants in the pilot-plant on the spot.The results indicate that the outlet water quality SDI 15<1.5,turbidity< 0.15 NTU,remaining chlorine<0.10mg/L,the treated water could meet the requirement of inlet water quality of reverse osmosis membrane.Reverse osmosis membrane desalting ratio is above 99% with stably treated water quality.This technology creates a newway for the treatment of circulating cooling system discharge water and has a good future for the application.
Su Jinpo, Tan Suli, Yin Lianqing, Mo Liping . Study on membrane technology used for the treatment of circulating cooling system discharge water of power plants[J]. Industrial Water Treatment, 2005 , 25(12) : 50 -53 . DOI: 10.11894/1005-829x.2005.25(12).50
[1] 林玲玲.浅谈热电厂水处理工艺模型的选择[J].工业水处理,2000,20(2):16-19
[2] 陈良刚,陈清.超滤膜用于反渗透的前置处理[J].膜科学与技术,2003,23(4):45-46
[3] 张赞红.超滤作为反渗透预处理的探讨[J].净水技术,2003,22(4):29-31
[4] 林和坤,周绗.盘式过滤器的原理和使用方法[J].工业用水和废水,2002,33(3):44-46
[5] 张捍民,王宝贞.淹没式膜过滤饮用水装置去除水中污染物试验研究[J].给水排水,2000,20(6):31-32
/
〈 | 〉 |