工业水处理 ›› 2015, Vol. 35 ›› Issue (12): 18-21. doi: 10.11894/1005-829x.2015.35(12).018

• 试验研究 • 上一篇    下一篇

再生水回用于工业冷却中有机污染物健康风险研究

徐圃青1,2, 邓文英1, 谢翠婷2, 文斌3, 孙佳4   

  1. 1. 常州市环境科学研究院, 江苏常州 213022;
    2. 常州大学环境与安全工程学院, 江苏常州 213164;
    3. 澳实分析检测(上海)有限公司, 上海 201206;
    4. 常州市环境监测中心, 江苏常州 213001
  • 收稿日期:2015-11-06 出版日期:2015-12-20 发布日期:2015-12-26
  • 通讯作者: 邓文英,E-mail:wydenghhu@163.com。 E-mail:wydenghhu@163.com
  • 作者简介:徐圃青(1965-),硕士,高工,E-mail:xpq6501@vip.sina.com。
  • 基金资助:

    国家水体污染控制与治理科技重大专项(2012ZX07301-001-01);江苏省太湖治理专项资金(kYH1102134C)

Study on health risk from organic pollulants in industrial cooling in reclaimed water reuse

Xu Puqing1,2, Deng Wenying1, Xie Cuiting2, Wen Bin3, Sun Jia4   

  1. 1. Changzhou Research Academy of Environmental Sciences, Changzhou 213022, China;
    2. College of Environmental and Safety Engineering, Changzhou University, Changzhou 213164, China;
    3. Australian Real Analysis Detection(Shanghai)Co., Ltd., Shanghai 201206, China;
    4. Changzhou Environmental Monitoring Center, Changzhou 213001, China
  • Received:2015-11-06 Online:2015-12-20 Published:2015-12-26

摘要:

建立了工业循环冷却水动态模拟试验系统,采集和分析了再生水在冷却塔热质交换过程中逸散到空气中的有机污染物,运用剂量-反应暴露评价模型,开展了空气中有机污染物对冷却塔周边工作的典型人群健康风险评估。结果表明,再生水中的有机污染物不会对暴露人群健康造成明显影响,卤代烃对健康风险的影响大于苯系物。城市污水处理厂是优质的再生水水源,应严格控制工业废水接入比例,减少卤代烃等难降解污染物,从源头控制风险。

关键词: 城市污水处理厂, 再生水, 工业冷却系统, 有机污染物, 健康风险

Abstract:

A dynamic simulation test system of industrial circulating cooling water has been established. The organic pollutants which were dissipated to the air during the course of cooling tower heat exchange from reclaimed water are collected and analyzed. Using the evaluation model of dosage-reaction exposure,health risk assessment for typical human groups who worked near the cooling tower has been carried out. The results indicate that,organic pollutants in reclaimed water cannot cause obvious influence on the health of exposed population groups. The effect of halogena-ted hydrocarbon on health risk is greater than that of benzene series. Urban sewage plant is the high-quality source of reclaimed water. The introduced proportion of industrial wastewater should be controlled seriously,so as to reduce halohydrocarbon and other bio-refractory pollutants. The risk should be controlled from the water sources.

Key words: urban sewage treatment plant, reclaimed water, industrial cooling system, organic pollutants, health risk

中图分类号: