INDUSTRIAL WATER TREATMENT ›› 2015, Vol. 35 ›› Issue (10): 42-45. doi: 10.11894/1005-829x.2015.35(10).042

Previous Articles     Next Articles

Study on reclaimed water disinfection with chlorine dioxide

Liu Yanjuan1, Ma Lisha2, Zhu Ming3, Yang Yawen4, Zhao Yan3   

  1. 1. Department of Environmental & Chemical Engineering, Tangshan College, Tangshan 063000, China;
    2. Institute of Hydrogeology and Environmental Geology, CAGS, Shijiazhuang 050803, China;
    3. China Meat Research Center, Beijing 100068, China;
    4. Beijing Municipal Institute of Labour Protection Science, Beijing 100054, China
  • Received:2015-07-30 Online:2015-10-20 Published:2015-10-22

二氧化氯消毒中水实验研究

刘艳娟1, 马丽莎2, 祝明3, 杨雅雯4, 赵燕3   

  1. 1. 唐山学院环境与化学工程系, 河北 唐山 063000;
    2. 中国地质科学院水文地质环境地质研究所, 河北 石家庄 050803;
    3. 中国肉类实验综合研究中心, 北京 100068;
    4. 北京市劳动保护科学研究所, 北京 100054
  • 作者简介:刘艳娟(1975—),硕士,副教授.电话:13011440003,E-mail:juan1809@163.com
  • 基金资助:

    唐山市重点实验室项目(09150202A-2);唐山学院科研立项项目(15001B)

Abstract:

The quantitative relationship between COD of chlorine dioxide used for disinfecting reclaimed water,and chlorine dioxide minimum dosage,and the residual dosage of ensuring continuous disinfecting capacity of chlorine dioxide have been studied. The results show that under the following conditions:at room temperature,COD is 15-50 mg/L,turbidity 1.00-6.37 NTU,the numbers of colon bacillus <106,the quantitative relationship between reclaimed water COD and the minimum dosage of chlorine dioxide meets the unary linear equation. To ensure the continuous disinfecting capacity of chlorine dioxide,the mass concentration of the residual chlorine dioxide of the water sample which has been disinfected for 30 min,should not be lower than 0.10 mg/L. The rule that chlorine dioxide concentration attenuates with time complies with the first level of reaction kinetics model. Furthermore,with the decrease of chlorine dioxide concentration,its attenuation rate decreases gradually.

Key words: chlorine dioxide, reclaimed water, disinfection, COD

摘要:

研究了二氧化氯消毒中水COD与二氧化氯最小投加量的定量关系及确保二氧化氯持续消毒能力的剩余剂量.结果表明:在室温,COD为 15~50 mg/L,浊度为1.00~6.37 NTU,大肠菌群数 <106数量级的条件下,中水COD与二氧化氯最小投加量定量关系满足一元线性方程.为保证二氧化氯的持续消毒能力,消毒30 min水样的剩余二氧化氯质量浓度不能低于0.10 mg/L.二氧化氯浓度随时间的衰减规律符合一级反应动力学模型,且随二氧化氯浓度的减小,其衰减速率逐渐减小.

关键词: 二氧化氯, 中水, 消毒, COD