Abstract:
The capacity of the counter flow cooling tower in No.1 Circulating Cooling Water System,which consists of 7 rooms,is increased by 50%,after having been reinforced and reformed by stages. The reforms in the counter flow cooling tower and their effects have been analyzed and evaluated. The drip stuffing,the choosing of water distributor and the improvement of air conduit system have been discussed. The two year running practice shows that the capacity of the counter flow cooling tower in No.1 circulating cooling water system is increased apparently, and can meet the requirements of the production with high efficiency.