火力发电厂生活污水处理回用于循环冷却水的中试研究

郭安祥1, 王立立2, 白晓春1   

  1. 1. 西北电力试验研究院, 陕西西安, 710054;
    2. 暨南大学环境工程系, 广东广州, 510601
  • 收稿日期:2004-02-26 出版日期:2004-12-20 发布日期:2010-10-01
  • 作者简介:郭安详(1971- ),1995年毕业于东北电力学院,研究方向:水处理技术.电话:(029)85763238,E-mail:gaxwy029@163.com

Pilot-scale study on reclaiming domestic wastewater as circulating cooling water in a heat power plant

Guo Anxiang1, Wang Lili2, Bai Xiaochun1   

  1. 1. Northwest Electric Power Test & Research Institute, Xi'an 710054, China;
    2. Department of Environmental Engineering, Jinan University, Guangzhou 510601, China
  • Received:2004-02-26 Online:2004-12-20 Published:2010-10-01

摘要:

通过曝气生物滤池的中试试验找到了火力发电厂低浓度生活污水处理回用于循环冷却水的新工艺,为火力发电厂实现废水零排放提供了技术依据。得出了BAF运行于电厂生活污水水质条件下的最佳水力负荷为3m3/(m2·h),其CODCr、BOD5、氨氮、SS平均去除率分别为78.21%、82.53%、86.97%、85.82%,相应出水平均水质为CODCr14.17mg/L、BOD53.72mg/L、氨氮0.40mg/L、SS3.67mg/L,满足于以合金铜管为凝汽器管材的循环冷却水水质标准。

关键词: 火力发电厂, 低浓度生活污水处理回用, 曝气生物滤池

Abstract:

Through a pilot-scale study of biological aerated filter(BAF),a new technology to reclaim the low concentrated domestic wastewater as circulating cooling water has been developed. In addition,the experiment can also provide some technical foundations of realizing zero drainage in a heat power plant,then we can conclude that the best hydraulic load for BAF's running under the condition which has low concentrated domestic wastewater in a power plant is 3m3/(m2·h). In this experiment, the average removal efficiency of CODCr,BOD5,NH3-N,SS is 78.21%,82.53%,86.97%,85.82% respectively. The average quality of the outlet is CODCr. 14.17 mg/L,BODS 3.72 mg/L, NH3-N 0.40 mg/L, SS 3.67 mg/L. In conclusion, using BAF, the outlet of the reclaimed wastewater can meet the water quality standard of circulating cooling water used for the steam condensers which is made of alloy copper pipes.

Key words: heat power plant, disposal and reclaimation of low concentrated domestic wastewater, biological aerated filter